Untitled
Technical specifications of UKS type boilers
| Detailed list |
Technical specifications of UKS type boilers |
| Boiler type | |
UKS 5 | UKS 6,5 | UKS 8 | UKS 12 | UKS 14 | UKS 19 | UKS 23 | UKS 27 | UKS 42 |
UKS 70 | UKS 95 | UKS 130 | UKS 190 |
UKS 250 | UKS 400 | UKS 560 |
| Size Range | |
I | II | III |
III dwukomorowy |
| Average operating power | kW |
5 | 6,5 | 8 | 12 |
14 | 19 | 23 | 27 |
42 | 70 |
95 | 130 |
190 | 250 |
400 |
560 |
| Boiler's heating surface | m2 |
0,6 | 0,8 | 1,0 | 1,5 |
1,8 | 2,6 | 3,2 | 4,0 |
6,0 | 9,0 |
12,0 | 16,0 | 24,0 |
32,0 | 50,0 | 70,0 |
| Heated area | m2 |
do 45 | 45- 55 | 55- 70 | 70- 90 |
90- 110 | 110- 130 | 130- 160 |
160- 200 |
200- 300 | 300- 500 |
500- 680 | 680- 930 | 930- 1370 |
1370- 1820 | 1820- 2850 | 2850- 3990 |
| Basic fuel | |
Hard coal type 32.1, class 26/9, OII grade, boiler coal type |
Hard coal type 32.1, class 26/12, OII grade, boiler coal type |
| Substitute fuel | |
| Mixture:
50%-hard coal type 32.1,
class 26/9, OII grade
50%-hard coal type 32.1, class 24/12, MI grade
|
Mixture:
50%-hard coal type 32.1,
class 26/12, OII grade
50%-hard coal type 32.1, class 24/15, MI grade
|
| Max. consumption of basic fuel at the rated power | kg/h |
0,98 | 1,26 | 1,54 | 2,3 |
2,6 | 3,6 |
4,3 | 5,0 | 7,7 | 13 |
17 | 23 | 33 | 48 |
76 | 107 |
| Single fuel charge | kg |
5 | 6,5 | 8 | 11 |
13 | 18 | 21 | 25 |
40 |
65 | 85 | 115 | 165 |
220 | 340 | 480 |
| Boiler water capacity | L |
28 | 32 | 36 | 81 |
115 | 143 | 151 | 225 |
371 |
505 | 702 | 875 | 1280 |
| | |
| Boiler weight without water | kg |
90 | 110 | 125 | 210 |
235 | 270 | 330 | 370 |
520 |
680 | 1020 | 1350 | 2077 |
2800 | 4400 | 5900 |
| Max. water temperature | [°C] |
90 |
| Combustion time | h |
Up to 12 |
| Max. working pressure | Bar |
1,0 |
1,5 |
2,5 |
| Test pressure | Bar |
| | | |
| | | |
| | | |
| | | |
| Efficiency - basic fuel |
% |
71 |
72 |
72 |
73 |
74 |
74 |
75 |
75 |
76 |
76 |
77 |
78 |
79 |
78 |
78 |
78 |
| Efficiency - substitute fuel |
% |
|
|
|
64 |
65 |
65 |
66 |
67 |
67 |
68 |
70 |
72 |
74 |
72 |
72 |
72 |
| Required flue gas draft | Pa |
20 | 22 | 25 | 20 |
20 | 22 | 22 | 25 |
25 | 35 |
35 | 35 | 40 |
42 | 45 | 50 |
| Required stack height | m |
5 | 5 | 5 | 5 |
5 | 5 | 5 | 7 | 7 |
8,5 | 9,5 |
10,5 | 11,0 |
12,0 | 13,5 |
14,5 |
| Required stack hole cross-section | cm2 |
196 | 196 | 196 | 294 |
294 | 294 | 441 | 441 |
441 | 588 | 784 |
980 | 1225 | 1600 |
2025 | 2500 |
| Diameters of supply connector pipe and return connector pipe | mm |
48x4 | 60x4 |
89x4,5 | 108x5 | 133x5 |
| Dimensions of flue cross-section |
mm |
100x100 |
150 x150 |
180 x180 |
190 x190 |
200 x200 |
210 x210 |
220 x220 |
260 x260> |
350 x300 |
400 x350 |
460 x350 |
500 x400 |
500 x450 |
500 x500 |
| Dimensions | Width |
mm | | 344 |
| 450 | 527 | 590 |
592 | 646 | 772 |
870 | 1060 | 1120 | 1323 |
1714 | 1986 | 2520 |
| Height |
923 | 923 | 923 | 856 |
910 | 910 | 995 | 1105 |
1180 |
1230 | 1320 | 1420 | 1570 |
1610 | 1890 | 2070 |
| Length with the flue |
630 | 690 | 750 | 1000 |
1110 | 1180 | 1385 | 1500 |
1500 |
1870 | 2100 | 2305 | 2740 |
2480 | 2910 | 3180 |
Boilers with the average operating power over 190 kW are made to order.
Modernized UKS-M type boilers
Universal steel boilers are designed to the combustion of low quality coal, fine coal, brown coal and wood.
While selecting a central heating boiler, the thermal balance of the heated area should be taken into account. The rated thermal efficiency of the boiler should be higher by 10% than the calculated heat requirement of the heated rooms. The table contains approximate areas of heated rooms, which may be heated by UKS type boilers. These data, based on our long-standing experience in assessing the level of room insulation and heat requirement, are approximate and refer to rooms with a height of 3 meters.
UKS-M type boilers (universal water heating boilers using fine coal as fuel) and UKS-G type boilers (universal water heating boilers using fine coal as fuel; UKS-G type boilers have an upper boiler pass, i.e., the boiler pass is placed above the boiler furnace) are the modernized versions of UKS type boilers and are designed to the combustion of low quality coal, fine coal, brown coal and wood. Their modern construction and the application of a microprocessor controller and blower makes it possible to burn fine coal going from the top to the bottom. As a result, it has a significant influence on reducing the environmental pollution. These central heating boilers operate in an average 24h working cycle.
UKS-M type boiler specifications
| Detailed list |
Technical specifications of UKS-M type boilers |
| Boiler type | |
12 | 14 | 21 |
25 | 30 | 46 | 71 |
97 | 130 | 190 |
| Average operating power | kW |
12 | 14 |
21 | 25 |
30 | 46 |
71 | 92 |
130 |
190 |
| Min. power. | kW |
3,5 | 4 |
6 | 7 |
9 | 14 |
21 | 29 |
39 |
57 |
Average operating power in a 24h working cycle | kW |
6 | 7 |
10 | 12 |
15 | 23 |
35 | 48 |
65 |
95 |
| Boiler heating surface | m2 |
1,5 | 1,6 |
2,5 | 3,0 |
3,7 | 5,5 | 8,5 |
11,5 | 15 | 22 |
Approximate heated area | m2 |
70- 90 |
90- 110 |
110- 130 | 130- 160 |
160- 200 | 200- 300 | 300- 500 |
500- 680 | 680- 930 | 930- 1370 |
Insulated building, new installation | m2 |
do 100 |
100- 150 |
150- 190 | 190- 230 |
230- 280 | 280- 400 | 400- 600 |
600- 850 | 850- 1050 | 1050- 1700 |
| Fuel type | |
Hard coal - fine coal MI grade, type 32.1 class 25/12 according to PN-82/G-97001-3 standard |
Max. basic fuel charge at the rated power | kg/h |
2,3 | 2,6 | 3,6 | 4,3 |
5,0 | 7,7 | 13 | 17 |
23 | 33 |
| Single fuel charge | kg |
11 | 13 |
18 |
21 | 25 | 40 | 65 |
85 | 115 | 165 |
| Boiler water capacity | L |
81 | 115 |
143 |
151 | 225 | 371 | 505 |
702 | 875 | 1280 |
| Boiler weight without water | kg |
210 | 230 |
260 |
310 | 360 | 480 | 680 |
1020 | 1350 | 2077 |
| Max. water temperature | [°C] |
90 |
| Combustion time | h |
8 do 24 |
| Max. working pressure | Bar |
1,0 |
1,5 |
| Test pressure | Bar |
4,0 |
Thermal efficiency - basic fuel |
% |
81 |
Thermal efficiency - substitute fuel |
% |
75 |
| Required flue gas draft | Pa |
20 | 20 |
22 | 22 |
25 | 25 | 35 |
35 | 35 | 40 |
| Required stack height | m |
5 | 5 | 5 |
4 | 7 |
7 | 8,5 |
9,5 | 10,5 |
11,0 |
Required stack hole cross-section | cm2 |
294 | 294 | 294 |
441 | 441 | 441 |
588 | 784 | 980 |
1225 |
| Diameters of supply connector pipe and return connector pipe | mm |
60x4 |
89x4,5 | 108x5 |
| Dimensions of flue cross-section |
mm |
150 x150 |
180 x180> |
190 x190 |
200 x200 |
210 x210 |
220 x220 |
260 x260 |
350 x300 |
400 x300 |
460 x350 |
Dimensions of UKSM type boiler | Width |
mm |
480 | 549 | 606 |
608 | 662 | 778 | 867 |
1066 | 1135 | 1338 |
| Height |
1005 | 1055 |
1055 |
1145 | 1255 | 1311 | 1360 |
1520 | 1620 | 1770 |
Length with the flue |
1000 | 1100 |
1180 |
1180 | 1375 | 1450 | 1820 |
2050 | 2255 | 2690 |
Modernized UKS-G type boilers
UKS-G type boiler specifications
| Detailed list |
Technical specifications of UKS-G (modernized) type boilers |
| Boiler type | |
15 | 18 | 20 | 24 | 33 | 38 |
43 |
| Average operating power | kW |
15 | 18 | 20 | 24 |
33 | 38 | 43 |
| Min. power | kW |
4 | 5 | 6 | 7 |
10 | 12 | 13 |
Average operating power in a 24h working cycle | kW |
7 | 9 | 10 | 12 |
16 | 19 | 21 |
| Boiler's heating surface | m2 |
1,5 | 1,8 | 2,0 | 2,4 |
3,3 | 3,8 | 4,3 |
| Approximate heated area | m2 |
70 -90 | 90- 110 | 110- 130 | 130- 160 |
160- 200 | 200- 250 | 250- 300 |
Insulated building, new installation | m2 |
do 130 | 130- 160 | 160- 180 |
180- 220 |
220- 280 | 280- 320 | 320- 380 |
| Single fuel charge | kg |
20 | 24 | 34 | 48 | 78 | 102 | 123 |
| Fuel type | |
Hard coal - fine coal MI grade, type 32.1 class 25/12 according to PN-82/G-97001-3 standard |
| Boiler water capacity | l |
55 | 61 | 73 | 86 |
106 | 121 |
136 |
| Boiler weight without water | kg |
190 | 220 | 255 | 275 |
335 | 360 | 395 |
| Loading door size | Height | mm |
200 | 200 | 200 | 200 |
200 | 200 | 200 |
| Width | 260 | 310 | 365 | 365 | 365 | 365 | 365 |
| Boiler furnace depth | mm |
290 | 290 | 340 | 380 |
470 | 490 | 510 |
| Boiler furnace width | mm |
260 | 310 | 370 | 370 |
420 | 470 | 520 |
| Loading chamber size | dm3 |
21 | 26 | 37 | 52 |
84 | 110 | 132 |
| Max. water temperature | [°C] |
90 |
| Combustion time | h |
8 to 24 |
| Max. working pressure | Bar |
1,0 |
| Test pressure | Bar |
4,0 |
| Thermal efficiency | Basic fuel |
% |
80 |
| Substitute fuel | 75 |
| Required flue gas draft | Pa |
20 | 20 | 22 | 22 |
25 | 25 | 25 |
| Required stack height | m |
5 | 7 |
Required stack hole cross-section | cm2 |
284 | 284 | 284 | 415 |
415 | 415 | 415 |
| Ø | 190 | 190 | 190 | 230 | 230 | 230 | 230 |
Dimensions of flue cross-section | Ø |
mm |
160 |
160 |
160 |
160 |
160 |
|
| [ ] |
Height |
|
160 |
160 |
| Width |
180 |
180 |
Dimensions of UKS-G type boilers
| UKS-G | Unit of measurement | 15 kW | 18 kW | 20 kW | 24 kW | 33 kW | 38 kW | 43 kW |
| A | mm | 1255 | 1255 | 1270 | 1330 | 1405 | 1450 | 1472 |
| B | mm | 1155 | 1155 | 1170 | 1232 | 1305 | 1350 | 1372 |
| C | mm | 357 | 402 | 460 | 460 | 508 | 560 | 605 |
| D | mm | 442 | 487 | 545 | 545 | 593 | 645 | 690 |
| E | mm | 455 | 455 | 475 | 500 | 543 | 550 | 570 |
| F | mm | 403 | 403 | 448 | 498 | 583 | 600 | 630 |
| G | mm | 767 | 767 | 870 | 920 | 1005 | 1020 | 1050 |
| H | mm | 1005 | 1005 | 1023 | 1083 | 1156 | 1200 | 1225 |
| I | mm | 200 | 200 | 200 | 200 | 200 | 200 | 200 |
| a | Ø | ¾" | ¾" | ¾" | ¾" | ¾" | ¾" | ¾" |
| b | Ø | 2" | 2" | 2" | 2" | 2" | 2" | 2" |
|